Epidemic Legionnaires' DiseaseAirborne Transmission Down a Chimney
Jeffrey D. Band, MD;
Martin LaVenture, MPH;
Jeffrey P. Davis, MD;
George F. Mallison, MPH;
Peter Skaliy, PhD;
Peggy S. Hayes;
Wendy L. Schell;
Hank Weiss, MS, MPH;
Daniel J. Greenberg;
David W. Fraser, MD
JAMA. 1981;245(23):2404-2407.
Abstract
 |  |
Between June 18 and July 9, 1979, Legionnaires' disease (LD) developed in 13 persons who had visited a hotel complex in Wisconsin. All had visited the part of the hotel that contains the restaurants and meeting rooms (building A). Legionnaires' disease occurred in 1% who had been exclusively in the meeting rooms and in 0.1% who had eaten only at the hotel restaurants. Furthermore, 1.5% exposed to meeting room 1 and none of those exposed only to the other meeting rooms had LD. Legionella pneumophila was isolated from water in the cooling tower on top of building A. Located within 5 m downwind of the cooling-tower exhaust, a chimney with an open damper allowed cooling-tower exhaust (as demonstrated by air tracer studies) to enter meeting room 1 via the fireplace. Although cases did not occur after the cooling-tower water was treated by continuous hyperchlorination and the chimney was sealed, a seven-day lag occurred between treatment and elimination of the organism from the tower water.
(JAMA 1981;245:2404-2407)
Author Affiliations
From the Bacterial Diseases Division, Bureau of Epidemiology, Center for Disease Control, Atlanta (Drs Band, Skaliy, and Fraser, Mr Mallison, Mr Greenberg, and Ms Hayes), and the Wisconsin State Division of Health, Madison (Dr Davis, Mr LaVenture, Mr Weiss, and Ms Schell).
Footnotes
Presented in part at the 13th annual meeting of the Society for Epidemiologic Research, Minneapolis, June 17, 1980.
Reprint requests to Center for Disease Control, Bacterial Diseases Division, Bureau of Epidemiology, Atlanta, GA 30333 (Dr Band).
CiteULike Connotea Del.icio.us Digg Reddit Technorati Twitter
What's this?
THIS ARTICLE HAS BEEN CITED BY OTHER ARTICLES
Hotel Sanitation Regulations and the Incidence of Sanitation- Related Disease Outbreaks: Are There Implications?
Reutter and Logomarsino
Journal of Hospitality & Tourism Research 1989;13:247-257.
ABSTRACT
Mode of Transmission of Legionella pneumophila: A Critical Review
Muder et al.
Arch Intern Med 1986;146:1607-1612.
ABSTRACT
A New Legionella Species, Legionella feeleii Species Nova, Causes Pontiac Fever in an Automobile Plant
HERWALDT et al.
ANN INTERN MED 1984;100:333-338.
ABSTRACT
Nosocomial Legionnaires' Disease Uncovered in a Prospective Pneumonia Study: Implications for Underdiagnosis
Muder et al.
JAMA 1983;249:3184-3188.
ABSTRACT
|