Nosocomial Legionnaires' Disease
Epidemiologic Demonstration of Cooling Towers as a Source
- Paul L. Garbe, DVM;
- Barry J. Davis, MSEHE;
- Jay S. Weisfeld, MD;
- Lauri Markowitz, MD;
- Patricia Miner, MPH;
- Frank Garrity, MD;
- James M. Barbaree, PhD;
- Arthur L. Reingold, MD
- From the Division of Bacterial Diseases (Drs Garbe, Markowitz, Barbaree, and Reingold) and the Hospital Infections Program (Mr Davis), Center for Infectious Diseases, and the Epidemiology Program Office (Dr Weisfeld), Centers for Disease Control, Atlanta; and the Rhode Island Department of Health (Dr Weisfeld) and Rhode Island Hospital (Ms Miner and Dr Garrity), Providence.
Abstract
Investigation of a recent outbreak of nosocomial legionnaires' disease—initially thought to be due to the documented presence of Legionella pneumophila in the hospital potable water—showed that aerosols from one or more cooling towers were the actual source of infection. From June 27 to Aug 25, 1983, nosocomial legionnaires' disease developed in 15 persons at a hospital in Rhode Island. Twelve (80%) of 15 case-patients occupied rooms in building 1, unit B, compared with eight (28%) of 29 control patients (odds ratio=10.8; 95% confidence interval=1.4 to 85.6). Subsequent investigation demonstrated that water in a cooling tower located 100 ft upwind of unit B was heavily contaminated with L pneumophila, serogroup 1, subgroup 1, 2, 4, 5. The same strain was isolated from nine of the patients and from the make-up water for the tower. Active surveillance during the ten months following decontamination of the cooling tower identified no additional cases of nosocomial legionnaires' disease, although the hospital potable water had not been treated. While recommendations have been made for controlling nosocomial legionnaires' disease by heating or hyperchlorination of hospital potable water, this outbreak demonstrates the importance of an adequate epidemiologic-environmental investigation in choosing the appropriate control strategy.
(JAMA 1985;254:521-524)
Footnotes
-
Reprint requests to Respiratory and Special Pathogens Epidemiology Branch, 1-5405, Centers for Disease Control, 1600 Clifton Rd NE, Atlanta, GA 30333 (Dr Garbe).